Customization: | Available |
---|---|
Certification: | CE |
Fan: | With Fan |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Increases Chiller COP And IAQ fresh air desiccant unit
1.Product features:
1. The counter-flow air supply design has high gas-liquid heat exchange efficiency, and the volume is more compact compared with the cross-flow air supply design, and the equipment occupies a smaller area of the computer room;
2. The super absorbent core is made of polymer fiber material through a series of processes such as compression molding, high temperature carbonization, bonding, curing, etc. It has the advantages of anti-aging, corrosion resistance, mildew resistance, and long service life;
Combined with the design of counter-flow air supply, it can effectively solve the common liquid-carrying problem in cross-flow air supply;
3. Advanced solution concentration control technology, the unit has stronger and more accurate dehumidification capacity, and the minimum fresh air humidity can be controlled at 4.3g/kg.
4. International standard, reliable operation:
a. The solution tank is integrally formed, and there is no risk of air leakage and liquid leakage;
b. The heat exchanger is made of titanium tube, which will never rust.
c. Refrigeration components, controller components, water pumps, fans and other main components are all internationally renowned brands, which are stable and reliable.
2.Introduction
Heat pump type liquid desiccant air conditioning is an air dehumidification equipment with solution (lithium bromide, lithium chloride, calcium chloride, etc.) as the working fluid, The unit is driven by a heat pump and adopts advanced solution dehumidification technology,through the solution to absorb or release water to the air, to achieve the adjustment the humidity of air.It is not an ordinary fresh air ventilator,it is a fresh air treatment equipment integrating cold and heat source, dehumidification section, regeneration section, filter section, air supply section and exhaust section,It is flexible in application, simple in operation, and energy-saving, and is suitable for occasions where dehumidification and cooling are required in harsh environments such as air pollution, toxicity, and odor.
3.working Principle
5.Product parameters
Unit Model | AHLD-N03A | AHLD-N06A | AHLD-N09A | AHLD-N12A | AHLD-N15A | |
Power supply | 3PH-380V -50Hz | |||||
Dehumidifying air m³/h | 1,000 | 2,000 | 3000 | 4,000 | 5000 | |
Exhaust air m³/h | 1,200 | 2,400 | 3600 | 4,800 | 6000 | |
cooling capacity (kw) | 9 | 19 | 28 | 37 | 46.7 | |
Dehumidifying capacity kg/h | 10.9 | 21.8 | 32.8 | 43.7 | 54.6 | |
Power kW | 3.1 | 5.8 | 9.2 | 12 | 15.5 | |
Compressor type | Fully closed scroll compressor | |||||
Throttle Modes | Thermal Expansion valve | |||||
Desiccant | R407C | |||||
Filter grade | Primary (G4) | |||||
Fan Type | Outer rotor centrifugal fan | |||||
Supply Air excess pressure Pa | 130 | 280 | 300 | 330 | 350 | |
Exhaust air excess pressure Pa | 130 | 240 | 250 | 260 | 270 | |
Noise dB(A) | 60 | 61 | 62 | 63 | 64 | |
Weight kg | 660 | 1050 | 1600 | 1850 | 2200 | |
L (mm) | 1400 | 1700 | 2080 | 2300 | 2500 | |
w (mm) | 1150 | 1300 | 1550 | 1700 | 1800 | |
H (mm) | 1300 | 1450 | 1810 | 1900 | 2000 | |
Supply Air Outlet (mm) | A | 500 | 630 | 750 | 850 | 1000 |
B | 285 | 400 | 450 | 500 | 600 | |
Exhaust air outlet (mm) | C | 600 | 730 | 850 | 950 | 1100 |
D | 285 | 400 | 450 | 500 | 600 | |
Return Air Outlet (mm) | E | 400 | 630 | 750 | 850 | 900 |
F | 315 | 420 | 500 | 550 | 650 | |
Fresh Air Outlet (mm) | J | 500 | 730 | 850 | 950 | 1050 |
K | 315 | 420 | 500 | 550 | 650 | |
Note: 1. Norminal cooling and dehumidification working conditions: fresh air dry bulb temp. 35ºC, wet bulb temp. 27ºC; return air dry bulb temp. 37ºC, RH 15%; supply air dry bulb temp. 35ºC,RH 8.6%. 2. Running enviroment: clean plant with retaining structure, story height less than 2.5m. 3. Auxiliary electric heat device is optional, suitable for devices which need to run whole year. |
6.Application